모델명 : ETCR4300
원산지 : CHINA
브랜드 : ETCR
The ETCR4300 Three Phase Digital Phase Volt-Ampere Meter is a well-developed full-automatic, multi-functional, digital, intelligent meter specifically designed for field testing, featuring high accuracy, high stability, low power consumption, easiness to use and so on. It can directly measure AC voltage and AC current without opening the measured circuit, phases between three voltages, three currents and phase between the voltage and current; in addition, the power factor and power of the circuit can be indirectly measured, it can also be used to distinguish three-phase sequence, transformer wiring group, inductive and capacitive circuits, test second circuit and bus differential protection systems, read the phase relationship between CTs of the differential protection, check the meter wiring right, repair lines and equipment, etc.
The ETCR4300 Three Phase Digital Phase Volt-Ampere Meter has well designed shell mould made of newest material, attach with shakeproof, skidproof, high insulation sheath, has a 240dots×160dots LCD screen, all the test data display on the screen simultaneously, vector diagram indication, and looks exquisite and comfortable. Meter equipped with USB-RS232 interface, can store 500 sets of data, through the system software upload stored data to the computer, implementing online real-time monitoring and historical inquires, dynamic display. Can read, save, report, print history data, etc.
The ETCR4300 Three Phase Digital Phase Volt-Ampere Meter (Intelligent Three Phase Digital Phase Volt-Ampere Meter) applies to electric power, petroleum chemical industry, metallurgy, railway, and meteorology, industrial and mining enterprises, scientific research institutions, measurement sector and so on. Especially for the electricity billing system and relay protection system.
Power Supply DC 9V Zi-Mn dry battery LR14 1.5V 6 PCS
Clamp Φ8mm
LCD 240dotsX160dots
Range Voltage:AC 0.00V~600V
Current:AC 0.0mA~20.0A
Phase:0.0°~360.0°
Frequency:45.00Hz~65.00Hz
Active power:0.0W~12kW
Reactive power:0.0VAR~12kVAR
Apparent Power:0.0VA~12kVA
Power factor:-1~+1
Current vector:0mA~60.0A
Resolution Voltage:AC 0.01V
Current:AC 0.1mA
Phase:0.1°
Frequency:0.01Hz
Active power:0.1W
Reactive power:0.1VAR
Apparent Power:0.1VA
Power factor:0.001
Current vector: 1mA
Accuracy ±0.5% range
Date Storage 500 sets
Data upload function USB interface, the stored data upload computer, easy to analyze management data
Auto Power-off 15 minutes off automatically
Power Consumption With backlight: MAX working Current about 70mA, the battery can work continuously for 8 hours
without backlight:working current about 50mA,the battery can work continuously for 12 hours
Working environment -10℃~40℃;below 80%Rh
Store environment -10℃~60℃; below 70%Rh
Phase sequence Positive: U1, U2, U3 or I1, I2, I3 The cursor flashes from left to right
Inverting: U1, U2, U3 or I1, I2, I3 The cursor flashes from right to left
The phase range of the measured signal when measuring phase Measuring U1-U2 phase: 30V ~ 500V
When measuring U1-I2 or I1-U2 phase: 10V ~ 500V, 10mA ~ 10.00A
Test line length 1.5m
Current clamp length 2m
measure time 2s/time
Data Hold Press the HOLD button during the test to hold the data, the "DH" symbol is displayed
input resistance Test voltage input impedance is:1MΩ
Low battery When battery voltage decreases to about 7.2V, battery voltage low icon " "will display, reminding to replace battery.
Withstanding Voltage Between the instrument line and the shell to withstand 1000V / 50Hz sine wave AC voltage for 1 minute
Insulation Between the meter line and the jacket shell ≥ 100MΩ
Structure Double insulated, with insulated vibration-proof jacket
Protection Type IEC61010-1 CAT Ⅲ 600V,IEC61010-031,IEC61326,Pollution 2
Weight 1310g
Dimension 196mm×92mm×54mm